How Can We Help?
KCX-B*W(M) replace

Question
I am continuously using KCX-B*W (KCX-B*WM).
I heard that it will be discountinued, which is the alternative model?

Answer
A similar model is the KCV series.
Since there are differences in specifications, please check the following notes when replacing.
-Notes-
If used under the following conditions, it can be replaced with KCX-*W (KCX-*WM).
– Input logic: Positive logic (SW4 B side)
– Output operation switching: Mode 0 or 2 (SW5)
– When counting only in one direction (only adding, only subtracting)
-> Click here for details.
Replacement
Model number comparison table
KCX-B series | KCV series | remarks |
---|---|---|
KCX-B4W | KCV-4S | 4-digit AC power supply |
KCX-B4WM | ||
KCX-B6W | KCV-6S | 6-digit AC power supply |
KCX-B6WM |
Notes
1. The external dimensions are different. (KCX: 72mm square ->KCV: 48mm square)
2. The maximum input speed is different. (KCX-B: 20kHz -> KCV: 10kHz)
3. The output current of the power supply for the sensor is different. (KCX: 80mA -> KCV: 60mA)
4. The KCV transistor output cannot be used in positive logic (PNP).
5. The terminal block arrangement and setup method are different between KCX-B and KCV.
6. KCX has no contact output / contact output for the first set value,
. There is also a non-contact output / contact output for the second set value,
. For KCV, the output of the first set value (with prediction output) is non-contact output,
. The output of the second set value is the contact output.
2. The maximum input speed is different. (KCX-B: 20kHz -> KCV: 10kHz)
3. The output current of the power supply for the sensor is different. (KCX: 80mA -> KCV: 60mA)
4. The KCV transistor output cannot be used in positive logic (PNP).
5. The terminal block arrangement and setup method are different between KCX-B and KCV.
6. KCX has no contact output / contact output for the first set value,
. There is also a non-contact output / contact output for the second set value,
. For KCV, the output of the first set value (with prediction output) is non-contact output,
. The output of the second set value is the contact output.
About operation
Operation Mode | OUT1 Counting | OUT1 Output | OUT2 Counting | OUT2 Output | Replaceability |
---|---|---|---|---|---|
0 | Continuous | Holding | Continuous | Holding | Available |
1 | Continuous | Holding | Continuous | One-shot | Unavailable |
2 | Continuous | Holding | Reset | One-shot | Unavailable |
3 | Continuous | One-shot | Continuous | Holding | Available |
4 | Continuous | One-shot | Continuous | One-shot | Unavailable |
5 | Continuous | One-shot | Reset | One-shot | Unavailable |
6 | Count value is the first set value or less | Count value is the second set value or more | Unavailable | ||
7 | Count value is the first set value or less | Count value is the first set value or more and the second set value or less | Unavailable | ||
8 | Count value is the second set value or more | Count value is minus | Unavailable | ||
9 | Count value is the first set value or more and the second set value or less | Count value is the second set value or more | Unavailable |
Input connection method

Output connection method

If the contact output is used for the KCX-B’s first set value output, an external relay is required at the time of replacement.

If a non-contact output is used for the second set value output of KCX-B, it will be a contact output after replacement.

Preset value
Both KCX-B / KCV are set with each digit key.
DIP switch setting

When replacing mode 0 (hold output / count continuation), SW5 of KCV is set to ON.
KCX-B’s Dip SW4 (input / output logic) settings are set in the KCV setup mode.
* The transistor output of KCV cannot be used in positive logic (PNP).
Settings in setup mode

Inquiry
technical support
Click here for inquiries by email
Click here for inquiries by email