Replace KCX-B*W(M) with KCX-*W(M)
Question
I have been using KCX-B*W (KCX-B*WM) continuously, but I heard that it has been discontinued.
I hear that KCX-*W(M) can be used as an alternative model depending on the usage, but could you please tell me specifically?
Answer
If used under the following conditions, it can be replaced with KCX-*W (KCX-*WM).
– Input logic: Positive logic (SW4 B side)
– Output operation switching: Mode 0 or 2 (SW5)
– When counting only in one direction (only incremet, only decrement)
Replacement
Model number comparison table
KCX-B series | KCX-W(M) series |
---|---|
KCX-B4W | KCX-4W |
KCX-B4WM | KCX-4WM |
KCX-B6W | KCX-6W |
KCX-B6WM | KCX-6WM |
If an encoder is connected to the input
Connect only either OUTA or OUTB of the encoder signal to the counting input of the counter.
When used in decrement mode
for example,
If you are using the first setting value: 100 and second setting value: 500,
The counter operation starts from 500, and when the count value reaches 100, OUT1 turns on.
When the count value reaches 0, OUT2 turns on
To do.
However, KCX-*W(M) cannot be subtracted in this way.
Therefore
First setting value: 400, second setting value: 500
The counter operation starts from 0, and when the count value reaches 400, OUT1 turns on.
When the count value reaches 500, OUT2 turns on
Please change the usage to .
If you are using the first setting value: 100 and second setting value: 500,
The counter operation starts from 500, and when the count value reaches 100, OUT1 turns on.
When the count value reaches 0, OUT2 turns on
To do.
However, KCX-*W(M) cannot be subtracted in this way.
Therefore
First setting value: 400, second setting value: 500
The counter operation starts from 0, and when the count value reaches 400, OUT1 turns on.
When the count value reaches 500, OUT2 turns on
Please change the usage to .
Output operation
If KCX-B*W(M) is used in mode 0, set KCX-*W(M) to B type operation (SW1 B side).
If KCX-B*W(M) is used in mode 2, set KCX-*W(M) to A type operation (SW1 A side).
If KCX-B*W(M) is used in mode 2, set KCX-*W(M) to A type operation (SW1 A side).