Question

Question

I would like to update the GC-70 series HMI.
Please tell me the successor model and update procedure when updating to the current product.

Answer

Answer

The GC-70 series is currently being replaced by the GC-A2 series, but it is not a fully compatible product.
In addition, F/W Ver0.1.1.0 Build01 or later (produced after January 2021), GC-7x compatibility mode with improved compatibility with the old series is now available.
The project migration procedure when using this is as follows.
For details, please read the explanation below from the model number comparison table.
hmi-11-1

Notes

1. A USB memory is required to download the project to the GC-A2 series.
2. Please check whether the connected device you are using is listed in “Vol_8_2_SCA2_SCREEN CREATOER 5 Edition”.
3.If you are using K-BASIC to control the screen, the switching speed may be slow.
* Please use the parts of Screen Creator Advance2 instead.
4. If you are making a push button SW using texture parts, the response speed of button operations may be slow.
* Please delete the texture before use.
5.Other display restrictions may occur due to changes in screen resolution.

Model number comparison table

GC-70 Successor GC-A2 Screen size External dimensions Panel cutout
GC-73LM-R GC-A24-RS *1 7.0 inch wide 800×480(WVGA) no change no change
GC-73LC-R
GC-73LCL-R
GC-73LM-S GC-A24 *1 7.0 inch wide 800×480(WVGA) no change no change
GC-73LM-RS
GC-73LC-S
GC-73LC-RS
GC-73LCL-S
GC-73LCL-RS
GC-76LC GC-A26 *2 10.4 inches 800×600(SVGA) no change no change

*1: The screen size / resolution is different.
*2: The screen resolution is different.

Replacement procedure

If you do not have a project on your computer, start with “Backing up from the GC-70 HMI to a USB memory”.

Open the project

1. Select the project from “Project”-> “Open” of SCREEN CREATOR 5 (hereinafter referred to as SC5) and press “OK”.
hmi-11-2

Download to USB memory

2. Attach the USB memory to the USB port of the personal computer.
3. Select “Project”-> “Download” of SC5.
4. Check “Copy to CF card”, “Compile all the screen again”, “Project file transmission and upload edit enable”.
hmi-11-3
5. Press “Build -> Transmit”.
6. Specify the drive name of the attached USB port and press OK.
hmi-11-4
7. When the transfer is complete, remove the USB memory.

* The next work is from “21.”.
* Please skip “Backup from GC-70 HMI to USB memory”.

Backup from GC-70 HMI to USB memory

11. Turn on the power of the GC-70 HMI and attach the USB memory to the USB port.
12. Press and hold the upper left corner of the GC-70 HMI screen to switch to the system screen.
hmi-11-5
13. Press “Download”.
14. Select “Backup”-> “System Transfer : Yes” and press “Next”.
hmi-11-6
15. Select “USB Mass Storage” and press “Start”.
hmi-11-7
16. When the backup is finished, remove the USB memory and turn off the power.

Switch the firmware of the GC-A2 HMI to “SC5 mode”

21. Attach the USB memory to the GC-A2 display.
22. If you turn on the power while touching the upper left corner of the GC-A2 HMI screen, the system screen will be displayed.
GCA_MainMenu
23. Touch “Settings”-> “Option”-> “SC5 FW”-> “yes” to restart the GC-A2 HMI as a GC-70 equivalent.
GCA_SettingsMenu GCA_OptionMenu GCA_SC5FW_Switch

Transfer from USB memory to HMI

24. Select “Download”-> “USB Mass Storage” from the system screen.
hmi-11-8
25. Press “Start” to start downloading the project.
hmi-1-10
26. When the download is complete, HMI will start.

GC-A2 display initial setting

27. Make the necessary settings for operation such as “Serial port setting” from “System setting” on the system screen.
hmi-1-11
28. After completing the settings, press “User Mode” to start operation as HMI.

Inquiry