How Can We Help?
Analog configuration volume

Question
I heard that SZ-4(D2-240) is used for the equipment, but it has already been abolished.
The successor is D2-263, but it uses the analog setting volume of the CPU module.
How can I replace this?

Answer
The analog setting volume is a function that directly changes the following registers.
The successor D2-263 does not have this function.
If the register value is changed frequently, consider using a display.
If you want to use it only when adjusting the device and do not change it after the adjustment is completed, consider using a handheld programmer (S-20P).
Analog setting volume function
Channel | ch1 | ch2 | ch3 | ch4 |
---|---|---|---|---|
Lower limit setting register | R7640 | R7642 | R7644 | R7646 |
Lower limit setting register | R7640 | R7642 | R7644 | R7646 |
Upper limit setting register | R7641 | R7643 | R7645 | R7647 |
Analog data storage register | R3374 | R3375 | R3376 | R3377 |
Inquiry
technical support
Click here for inquiries by email
Click here for inquiries by email