EPSK Wiring

Question
I purchased it, but I don’t know how to wire the I/O.

Answer
Please wire referring to the diagram below.
Please read the precautions regarding power supply and terminal block wiring.
Note : Power Supply
Prepare a dedicated power supply for each module and input/output I/O power supply.
If the power supply for the module and the input/output I/O power supply are the same, if a short circuit (ground fall) occurs in the input/output I/O power line, a communication error will occur and the base unit will not be able to receive diagnostic information. .
If the power supply for the module and the input/output I/O power supply are the same, if a short circuit (ground fall) occurs in the input/output I/O power line, a communication error will occur and the base unit will not be able to receive diagnostic information. .
Note : Wiring
Due to the terminal block specifications, crossover wiring across 0V terminals is not possible.
When bundling the input common wire, make sure that the current is 90mA or less.
*Please note that the “short circuit (ground fall) function” will not work for inputs that do not have a common(+0,+1—+E,+F) wired.
When bundling the input common wire, make sure that the current is 90mA or less.
*Please note that the “short circuit (ground fall) function” will not work for inputs that do not have a common(+0,+1—+E,+F) wired.
Input(Proximity Sensors 3-wire)
Input(Proximity Sensors 2-wire / Switch)
Output