Modbus Address

Question

QuestionS

I would like to communicate with an HMI or other company’s PLC using Modbus/RTU.
Please tell me the Modbus address that corresponds to each function memory of JX-Series.

Answer

Answer

Select Address Pinker from Program in the JX-Programmming Tool menu.

Address comparison table

If you check the Display Modbus address check box, you can check the Modbus address corresponding to each function memory.
JX-Series GC-A2(ModbusRTU)
Name Address Name Address
Inputs X001–X816 Input Status 100001-100272
Inputs(word) XD0-XD8 Input Register 357345-357361
Outputs Y001-Y616 Coil 008193-008464
Outputs(word) YD0-YD8 Holding Register 457857-457873
Control Relay C1-C2000 Coil 016385-018384
Timer T1-T500 Input 145057-145556
Timer Cureent Value TD1-TD500 Holding Register 445057-445556
Counter CT1-CT250 Input 149153-149402
Counter Cureent Value CTD1-CTD500 Holding Register 449153-449651
System Control Relay SC1-SC1000 Input 161441-162440
Data Register DS1-DS4500 Holding Register 400001-404500
Data Register DD1-DD1000 Holding Register 416385-418383
Data Register DH1-DH500 Holding Register 424577-425076
Data Register DF1-DF500 Holding Register 428673-429671
Text Data Buffer TXT1-TXT1000 Holding Register 436865-437364
System Data Register SD1-SD1000 Input Register 361441-362440

Address of Inputs,Outputs,Input register,Inputs(word),Outputs(word)ter,and Text Data Register are discontinuous.
Please check the screen carefully.