AD/DA expansion of JX-BASIC-EX2

Question
        JX-BASIC-EX2 has analog inputs and outputs, but I don’t have enough.
        Can I add more?
    

Answer
        We are planning to develop an expansion board in the future, but currently there is no expansion board.
        (4ch expansion analog input: Scheduled to start selling in June 2024)
        Consider a remote I/O system using Modbus/RTU using the RS-485 port.
        (Or Modbus/TCP using the ethernet port)
        
        As the number of expansion cards increases, the refresh rate of remote I/O will decrease.
        Please download the sample program below.
    
Sample programm (Serial Port)
Example of keeping AD/DA data during communication error
            Download here
            -Master-
            Set the station number of Port3 to #1.
            The Send command writes the data registers DF15-DF16 of the master station to the data registers DF5-DF6 that are set as the analog outputs of the slave stations.
            Conversely, the Receive command reads the data registers DF1-DF4 that are set as the analog inputs of the slave stations to the data registers DF11-DF14 of the master station.
            -Slave-
            Set the station number of Port3 to #2.
            Configure the analog input/output settings.
            Only END command.
Example of setting AD/DA data to ZERO when there is a communication error
            Download here
            -Master-
            The scan counter (SD9) is copied to DF17 and written together with the analog output data (DF15-DF16) using the Send command.
            If the execution of the Receive command results in an error, the analog input registers DF11-DF14 are set to zero.
            -Slave-
            DF17 is monitored, and if there is no change for a certain period of time (1Sec), the analog output data DF15-DF16 is set to zero.
    
Sample programm (Ethernet Port)
Change the port for the ladder’s Send/Receive commands to “Port1.”
Inquiry
Click here for inquiries by email
