Question

Question

Can I connect the “Pon Zuke Box” to a touch panel other than JTEKT Electronics?

Answer

Answer

– When connecting via serial communication (RS-485), any device that supports our PLC or Modbus/RTU protocol can be connected.
– When connecting via Ethernet communication, any device that supports Modbus/TCP or EtherNet/IP protocols can be connected.
(The touch panle/computer is the master, and the “Pon Zuke Box” is the slave)
See below for details.

Serial Communication

Please connect to Port2 of SJ-ETHER with built-in “Pon Zuke Box”.
For the communication conditions of Port2, use KPP (Kostac PLC Programming software) and set Port2 from the PLC Port settings of the PLC.

Modbus/TCP Communication

Please connect to Port23 of SJ-ETHER with built-in “Pon Zuke Box”.
For the communication conditions of Port3, use KPP (Kostac PLC Programming software) and set Port3 from the PLC Port settings of the PLC.
Please see here for setting method

EtherNET/IP Communication

Please connect to Port3 of SJ-ETHER with built-in “Pon Zuke Box”.
Please see here for setting method

Address to use

Item PLC register Modbus Holding Register
1.Number of passes R2000–R2001 401025–401026
2.Number of failures R2002–R2003 401027–401028
3.Operating time(S) R2004–R2005 401029–401030
4.Stop time(S) R2006–R2007 401031–401032
5.Idle time(S) R2010–R2011 401033–401034
6.Total time(S) [3]+[4]+[5] R2012–R2013 401035–401036
7.Usage(%) [3]/[6] R2014–R2015 401037–401038
8.Cycle time(S) R2016–R2017 401039–401040
9.Number of plans R2020–R2021 401041–401042
10.Progress rate(%) [1]/[9] R2022–R2023 401043–401044
11.Pass rate(%) [1]/([1]+[2]) R2024–R2025 401045–401046

* Data is double word