Parallel connection (OR) / Series connection (AND)

Question

Question

I want to connect proximity sensors in parallel (series).
Is it possible?

Answer

Answer

DC 2-wire system (DC2W)

Parallel connection (OR) and Series connection (AND) are not possible.

DC 3-wire system (DC3W)

Parallel connection (OR) and series connection (AND) are possible.
Click here for details.
(See the “Outline” chapter)

About the number of connectable devices

Parallel connection (OR)

The “off-state current” of APS4-12S-E is less than 0.1mA.
When the “minimum on-current” of the connected PLC input module is 4.5mA
Theoretically, 4.5 / 0.1 = 45 units can be connected in parallel.

Series connection (AND)

The “voltage drop” of APS4-12S-E is 1.0V or less.
If the minimum on-voltage of the connected PLC input module is 19V
Theoretically, (24 – 19) / 1.0 = 5 units can be connected in series.(For DC24V)