How to collectively communicate scattered data

Question

Question

I would like to read and write data from an AC servo system.
Modbus communication addresses are scattered, and communication is not completed with one communication (one packet), resulting in poor communication efficiency.
What can I do to improve communication efficiency?

Answer

Answer

User’s Manual Chapter 8 8.3 P0.xxx Please use the mapping parameters in the monitoring parameters.
Set the mapping parameter code number you want to read to P0.035 on the panel or via communication.
Accessing the data at P0.025 corresponds to the same operation as accessing the parameter specified at P0.035.
Please see the explanation on P0.035 for the parameter setting method.
There are 8 mapping parameters in total. (1:P0.025 to 8:P0.032)

Setting example

servo-14-1