Modbus/RTU Error Code

Question

Question

An error occurs when communicating with an AC servo system using Modbus/RTU.
How can I check the error details?

Answer

Answer

Please refer to the error code table below.
The number of data that can be read at one time is 10 words, and the number of data that can be written at one time is 8 words.

Error Code

Error Code Error Contents
0x01 An attempt was made to read/write a group that does not exist.
0x02 An attempt was made to read/write a parameter that does not exist.
0x03 The value you tried to write is outside the minimum/maximum range.
0x04 The number of data you tried to read/write exceeds the upper limit.
(Read: 10 words , Write: 8 words)
0x05 The number of data you tried to read/write is zero.
0x06 The address you tried to write to is read-only or a parameter whose usage is pending.
0x28 password error
0x29 An attempt was made to write to an item that cannot be set while the servo is ON.
0x35 An odd numbered address was set as the start address.
0x36 An attempt was made to read/write 16 bits to 32 bits data.