JX-BASIC-EX2

Thin and space-saving board type controller available from March 2024

Board type controller with enhanced functionality from JX-BASIC

This product shares the JX-BASIC features of being "thin and space-saving" , "20 instructions, no manual required". If you are already using a similar product or would like to replace your microcomputer board, please consider using this product.

【Features】
・ Based on the board type controller "JX-BASIC", equipped with Ethernet port, increased number of inputs and outputs, and additional analog inputs and outputs
・ In addition to sink output type, source output type is also available
・ I/O board extendable for a variety of applications
・ Equipped with various interfaces as standard, ideal for combination with various devices
・ The wide variety of instructions used in general PLCs are consolidated into about 20 easy-to-understand instructions

【Free software available】
JX Programming Software

【Optional products】
・JX-40CDD1 (Sink output), JX-40CDD2 (Source output): Extension IO board
・ JX-04ADC: Extension analog input board

Specification

Product Specifications

  • Product name:JX-BASIC-EX2
  • Model number:JX-02DD1-D (Sink output), JX-02DD2-D (Source output)
  • Board size (mm):180×80mm
  • Power:24V DC *2
  • Memory retention:Available (always retained)
  • Calendar function:Available Secondary battery (no replacement required, non-removable)
  • I/O Input:24V DC, 16 points (16 points / common) (12 general-purpose points / 4 high-speed points), Sink/source, AWG28, 30P MIL connector *2
  • I/O Output (Sink):5~24V DC/0.3A, 16 points (8 points/common) (13 general purpose points/3 high speed points), AWG28, 34P MIL connector *2
  • I/O Output (Source):12~24V DC/0.3A, 16 points (8 points/common) (13 general purpose points/3 high speed points), AWG28, 34P MIL connector *2
  • Analog input
    • No. of points:4ch
    • Resolution:12bit
    • Range:Voltage: 0 to 10 V / Current: 0 to 20 mA / Thermistor: 0 to 3 V
    • Insulation:Non-insulated
    • Connection:5P connector *2
  • Analog output
    • No. of points:2ch
    • Resolution:12bit
    • Range:Voltage: 0 to 10 V / Current: 0 to 20 mA
    • Insulation:Non-insulated
    • Connection:2P connector *2
  • Serial communication
    • Communication protocol:Modbus RTU (Master / Slave), general purpose communication (ASCII)
    • RS-232C:6P connector *2
    •  RS-485: 3P connector *2
  • Ethernet communication
    • Communication protocol:Modbus TCP (Master / Slave), EtherNet/IP (Target), MQTT (Client), SMTP, E-mail (Send)
    • Port:RJ45 *2
  • USB:Programming port Micro USB Type-B
  • LEDs:Power, RUN, Error, I/O

 

Performance Specifications

  • Control method:Stored program cyclic calculation processing method
  • Program language:Ladder
  • Number of instructions:20 basic instructions
  • Minimum scan time:1msec
  • Scan time:1 msec ~ 10000 msec (Default MAX 200msec)
  • Program memory capacity:32000 steps
  • Function memory capacity:30k byte
  • Program storage:FLASH ROM
  • Power outage retention:Available
  • Mode switch:None
  • Programming:JX Programming (operating environment: Windows 10/11)

 

Extended IO Product Specifications *1

  • Applicable controller::JX-BASIC-EX2
  • Model number:JX-40CDD1 (Sink output), JX-40CDD2 (Source output)
  • Size (mm):180×80mm
  • I/O Input:24V DC, 24 points (24 points / common), Sink / Source, 40P MIL connector *2
  • I/O Output (Sink):5〜24V DC/0.3A, 16 points (8 points / common), 34P MIL connector *2
  • I/O Output (Source):12〜24V DC/0.3A, 16 points (8 points / common), 34P MIL connector *2

 

Extended analog input product specifications *1

  • Applicable controller::JX-BASIC, JX-BASIC-EX2
  • Model number:JX-04ADC
  • Size (mm):112×77 mm
  • Analog input
    • No. of points:4ch
    • Resolution:12bit
    • Range:Voltage: 0 to 10 V / Current: 0 to 20 mA / Thermistor: 0 to 3 V
    • Insulation:Non-insulated
    • Connection:20P terminal block (plug included)

*1:Up to 2 expansion boards can be available.
*2:Please prepare by yourself.